Model No.:  SZ11 Series On-load-tap-changing

Product Description Model NO.: SZ11 Series On-load-tap-changing Phase: Three Cooling Method: Oil-Immersed Type Transformer Certification: ISO9001-2000, ISO9001, CCC Frequency Characteristics: 50-60Hz Brand: Keyuan Rated Capacity: 100kVA-2500kVA Product Name: 11kv 33kv 415V 100kVA Three Phase Transformer Tap Range: ±5 or ±2X2.5% Vector Group: Dyn11 or Yyn0 Primary Voltage: 6kv/ 6.3kv/ 10kv/ 10.5kv/ 11kv/ 13.2 Kv Transport Package: Wooden Case Origin: China Application: Power, Electronic, Lighting Coil: Core-type Transformer Winding Type: Two-winding Transformer Usage: Power Transformer Shape of Coil: Ring Secondary Voltage: 0.4kv/10kv Color: Green Product Model: Sz11 Series on-Load-Tap-Changing Type: Oil Immersed Frequency: 50Hz ,60Hz Trademark: KEYUAN Specification: 100KVA-2500KVA HS Code: 8504 11kv 33kv 415V 100kVA Three Phase Transformer  
11kv 33kv 415V 100kVA Three Phase Transformer

SZ11 Series On-load-tap-changing Power Transformer

1. Brief Description
SZ11 series on-load-tap-changing Oil-Immersed Transformer is an upgraded product developed based on S11 series oil-immersed transformer. The voltage fluctuation and load change of power grid lead to fluctuation of output voltage of transformer during the running. If the voltage is too high or too low, the electric equipment will fail to work normally and even be burnt, and the insulation and efficiency of the transformer will be influenced. To ensure the variation of the output voltage within a reasonable range, voltage regulation is necessary. The product may operate the on-load tap changer manually or automatically to regulate the voltage when it is loaded, or realize remote voltage control through a controller.

2. Application Scope
The product applies to the users who require stable voltage and the voltage fluctuation of power grid is big.

3. Model Description
 
11kv 33kv 415V 100kVA Three Phase Transformer
4. Standards
GB 1094.1, GB 1094.2,GB 1094.3,GB 1094.5,
IEC 60076-1:2000,IEC 60076-2:1993, IEC 60076-3:2000, IEC 60076-5:2006
,GB/T 6451,GB/T 20052,etc
 
GB 1094.1, GB 1094.2, GB 1094.3, GB 1094.5,
IEC 60076-1:2000, IEC 60076-2:1993, IEC 60076-3:2000, IEC 60076-5:2006,
GB/T 6451, GB/T 20052, etc
5. Normal Service Conditions
Height above sea level: Not greater than 1,000m;
Ambient temperature: Maximum temperature: +40ºC;
Maximum daily average temperature: +30ºC;
Maximum annual average temperature: +20ºC;
Minimum outdoor temperature: -25ºC;
Installation environment: ground acceleration caused by earthquake: ag

Contact us if you need more details on Transformer. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Flyback Transformer、Power Transformer. If these products fail to match your need, please contact us and we would like to provide relevant information.